2019 Mobile Catalog

174 APPENDIX bluesea.com DC Main Circuit Protection and Branch Circuit Protection Purpose Fuses and circuit breakers are used to protect wire insulation from melting and starting fires in the event of overcurrents or short circuits which cause more amperage to flow in a wire than that wire is rated to carry. It is important to note that, except for those wires that are intended to carry starting currents, every positive wire in the DC Main Power Distribution System must be protected by a fuse or circuit breaker. Considerations for DC Main Circuit Protection Mounting Placement − distance from power source. The DC Main circuit protection system uses circuit breakers or fuses to protect the wires of the DC Main distribution system. For reference the American Boat and Yacht Council (ABYC) publishes voluntary standards for the type and placement of the fuse or circuit breaker to be used as a DC Main circuit protection device. Wire intended to carry engine starting currents between the batteries, the switch, and the starter is not required to have main circuit protection devices installed. Maximum mounting placement dimensions for a fuse or circuit breaker are 7" if the conductor is not housed in a sheath or enclosure in addition to the wire insulation, 40" if the conductor is housed in a sheath or enclosure in addition to the wire insulation, and 72" if the conductor is connected directly to the battery and housed in a sheath or enclosure in addition to the wire insulation. Selecting DC Main Circuit Protection The principal attribute of a DC Main circuit protection device is its Ampere Interrupt Capacity (AIC) rating. Specifications listed in the ABYC standards determine the AIC a DC Main circuit protection device must have. The required AIC rating is determined by the total CCA of the batteries connected to the circuit. See the tables at right for the required AIC ratings. Wire selection for DC applications on vehicles is usually based on voltage drop requirements. However, there is a maximum continuous current that the wire can withstand without overheating. Higher grade wires are rated for service up to 105°C (221°F)—the ABYC wire capacity table for 105°C is most frequently quoted. The 105°C table accurately reflects the capacity of single conductors exposed to freely circulating cooling air. However, other factors, such as covering bundles of wire in outer jackets to form a cable, or use of conduits or structural voids to protect wires, can reduce the cooling and reduce the safe capacity of the wire. A more conservative strategy is to use the 105°C wire, but treat it according to the 75°C table above when selecting circuit protection unless the wire is openly exposed for cooling. Total Connected Battery Cold Cranking Amperes (CCA) * Ampere Interrupt Capacity 12 VOLTS AND 24 VOLTS The white boxes identify two batteries, of the same size, placed in parallel configuration. DC MAIN DC BRANCH 650 CCA or Less 1,500 AIC 750 AIC 651–1,100 CCA 3,000 AIC 1,500 AIC Over 1,100 CCA 5,000 AIC 2,500 AIC 32 VOLTS 1,250 CCA or Less 3,000 AIC 1,500 AIC Over 1,250 CCA 5,000 AIC 2,500 AIC G24 G27 OR OR 8D 4D 4D OR OR G24 G24 G27 G27 4D ABYC E-11 Fuses under 10 Amp rating generally have such a high internal resistance they prevent fault currents from reaching 1000 Amps in 12 Volt circuits. The apparent contradiction when using these fuses for bilge pumps and other circuits directly off the battery is less of an issue than it might seem. If a fuse blows, and the case appears to be cracked or metal has been ejected, the fuse holder should be replaced. ABYC Interrupt Rating Table † Thermally limited amperage capacity See the Blue Sea Systems Circuit Wizard at circuitwizard.bluesea.com or page 170 for more assistance with wire and circuit protection selection. Standard Metric 75°C 90°C 105°C 75°C 90°C 105°C Ohms /1000ft Ohms /1000m AWG mm² Eng Rm Eng Rm Eng Rm Eng Rm Eng Rm Eng Rm mm dia 0.75 9.5 7 19 15.5 19 16 6.6 5.0 13 11 13 11 0.98 7.29 23.92 18 0.82 10 8 20 16 20 17 7 5 14 12 14 12 1.02 6.67 21.88 1.0 13 10 21 17 21 18 9 7 15 12 15 13 1.13 5.47 17.94 16 1.3 15 11 25 21 25 21 11 8 18 14 18 15 1.29 4.17 13.70 1.5 16 12 24 20 29 24 11 9 17 14 20 17 1.38 3.65 11.96 14 2.1 20 15 30 25 35 30 14 11 21 17 25 21 1.63 2.63 8.63 2.5 21 16 34 28 38 32 15 11 23 19 26 22 1.78 2.19 7.18 12 3.3 25 19 40 33 45 38 18 13 28 23 32 27 2.05 1.65 5.42 4.0 34 25 46 38 51 43 24 18 32 27 35 30 2.26 1.37 4.49 10 5.3 40 30 55 45 60 51 28 21 39 32 42 36 2.59 1.04 3.41 6.0 53 40 57 47 65 55 37 28 40 33 45 39 2.76 0.91 2.99 8 8.4 65 49 70 57 80 68 46 34 49 40 56 48 3.27 0.65 2.14 10.0 79 60 84 69 100 85 56 42 59 48 70 60 3.6 0.55 1.79 6 13.3 95 71 100 82 120 102 67 50 70 57 84 71 4.1 0.41 1.35 16.0 105 79 113 93 134 114 73 55 79 65 94 80 4.5 0.34 1.12 4 21 125 94 135 111 160 136 88 66 95 78 112 95 5.2 0.26 0.85 25 141 106 150 123 175 148 99 74 105 86 122 104 5.6 0.22 0.72 3 27 145 109 155 127 180 153 102 76 109 89 126 107 5.8 0.21 0.67 2 34 170 128 180 148 210 179 119 89 126 103 147 125 6.5 0.16 0.53 35 173 130 186 153 217 185 121 91 130 107 152 129 6.7 0.16 0.51 1 42 195 146 210 172 245 208 137 102 147 121 172 146 7.3 0.13 0.42 50 220 165 235 193 273 232 154 116 164 135 191 163 8.0 0.109 0.36 0 54 230 173 245 201 285 242 161 121 172 141 200 170 8.3 0.102 0.34 00 68 265 199 285 234 330 281 186 139 200 164 231 196 9.3 0.081 0.27 70 274 206 292 239 341 289 192 144 204 168 238 203 9.4 0.078 0.26 000 85 310 233 330 271 385 327 217 163 231 189 270 229 10.4 0.064 0.21 95 334 251 357 293 413 351 234 175 250 205 289 246 11.0 0.058 0.19 0000 107 360 270 385 316 445 378 252 189 270 221 312 265 11.7 0.051 0.17 120 387 290 414 339 478 406 271 203 290 237 335 284 12.4 0.046 0.15 150 445 333 476 390 550 467 311 233 333 273 385 327 13.8 0.036 0.12 REFERENCE DATA WIRE SIZE ABYC Ampacity Rating Table at 30°C † TEMPERATURE RATING OF CONDUCTOR INSULATION Data based on E-11 Table VI-A (single conductors in free air) Data based on E-11 Table VI-B (Up to three conductors in a sheath, conduit or bundle) SAE conductors are smaller than equivalent AWG by 5% to 12% with current capacity typically less by 7%. ISO Ratings for metric wire are slightly less than these values derived from ABYC VI-A ratings. • For bundles of 4 to 6 conductors multiply by 0.857 • For bundles of 7 to 24 conductors multiply by 0.714 • For bundles of 25 or more, conductors multiply by 0.571 Wires counted in bundles need not include: 1. Wires carrying intermittent currents no more than rating per VI-A and for less than one minute per mm of diameter, and not repeating more often than a delay of 5X times active duration. 2. Wires carrying load currents at less than 50% of the wire rating per table VI-B. * Battery cold cranking performance rating at -17.8°C (0°F): The discharge load in amps that a battery at -17.8°C (0°F) can deliver for 30 seconds, and maintain a voltage of 1.2 Volts per cell or higher, (e.g. 7.2 Volts for a 12 Volt battery). The CCA for the battery icons in this chart is an approximation and could be slightly higher or lower. Consult the battery manufacturer’s specifications for precise CCA ratings. A battery rated in MCA will have a CCA capacity approximately 80% of MCA

RkJQdWJsaXNoZXIy MjgzMDI=