Table of Contents Table of Contents
Previous Page  224 / 244 Next Page
Information
Show Menu
Previous Page 224 / 244 Next Page
Page Background

G e n e r a l

Industry Standards

224

toll free 800.334.5214 ACME ELECTRIC |

hubbell-acmeelectric.com

Underwriters’ Laboratories, Inc. is an independent not for profit organization which tests products for safety.

Acme’s transformers are designed and manufactured to comply with UL Standard 506, 1561, 1012, or 1062 and carry the

applicable UL Listing Label. Because of the continuous product evolutions at Acme, it is best that you contact the factory for the

current file and guide numbers associated with the listings.

The Canadian Standards Association is the Canadian counterpart to Underwriters’ Laboratories. Acme’s transformers are also

constructed and rated to comply with CSA Standards C22.2-47 and C22.2-66 and carry the CSA Certification Label.

All of Acme’s transformers are manufactured to meet National Electrical Code requirements.

Other Agencies and Standards:

National Electrical Manufacturers Association (NEMA)

ST-20 1992 (R1978)

American National Standards Institute (ANSI)

OSHA

IEEE

Listed

Certified

B

LOAD

A

SUPPLY

VOLTAGE

OCP LOCATION

How to overcurrent protect (OCP) 600 volt class transformers and associated wiring in accordance with the

‘99 National Electric Code (Articles 450-3(b) and 240-3 (i))

Primary

Secondary

Case

Type of

Supply Voltage

Phase

Number of

Wires on

Secondary

Protection

Required

OCP Location

Current

(amps)

OCP

(% of Rating)

Current

(amps)

OCP

(% of Rating)

1

Main

10

2

Primary Only

A

>9

<9, >2

<2

125

167 Maximum

300 Maximum

Not Required

2

Main

10

30

More Than 2

Not Applicable

Primary and

Secondary

A and B

>9

<9, >2

<2

125

167 Maximum

300 Maximum

>9

<9

125

167 Maximum

3

Feeder Circuit

with OCP

10

2

None on Either

Not Required

Not Required

4

Feeder Circuit

with OCP

10

30

More Than 2

Not Applicable

Secondary

Only

B

Not Required

9

<9

125