ACM_CAT_007_0913 - page 107

ACME ELECTRIC
MILWAUKEE, WI
800.334.5214
acmetransformer.com
107
SECTION
PANEL-TRAN
®
ZONE POWER CENTERS
Circuit Breaker Data
|
480 VOLTS DELTA TO 208Y/120 VOLTS
SELECTION CHARTS
THREE PHASE
GROUP A
{
The number of secondary circuits shown is only a representation of circuits. Please contact the factory for exact number of secondary circuits available.
|
10,000 Amps RMS Symmetrical Interrupting Capacity.
480 DELTA PRIMARY VOLTS –– 208Y/120 SECONDARY VOLTS –– 3Ø, 60 Hz
GROUP A – 304 SS
304 STAINLESS STEEL
480 DELTA PRIMARY VOLTS –– 208Y/120 SECONDARY VOLTS –– 3Ø, 60 Hz
MAX. SECONDARY CIRCUITS
{
APPROX. DIMENSIONS
APPROX.
INCHES (CM.)
NET WEIGHT
KVA
CATALOG NO.
120 V
208 V
HEIGHT
WIDTH
DEPTH
LBS. (KG.)
(1-Pole)
(3-Pole)
9.0
PTBA3150009LS
12
4
33.75 (85.7)
22.13 (56.2)
7.63 (19.4)
255 (116.0)
15.0
PTBA3150015LS
12
4
35.13 (89.2)
22.13 (56.2)
12.38 (31.4)
385 (175.0)
22.5
PTBA3150022LS
18
6
38.25 (97.2)
30.25 (76.8)
13.38 (34.0)
535 (243.0)
30.0
PTBA3150030LS
24
8
43.75 (111.1)
33.00 (83.8)
13.75 (34.9)
680 (308.0)
MAX. SECONDARY CIRCUITS
{
APPROX. DIMENSIONS
APPROX.
INCHES (CM.)
NET WEIGHT
KVA
CATALOG NO.
120 V
208 V
HEIGHT
WIDTH
DEPTH
LBS. (KG.)
(1-Pole)
(3-Pole)
9.0
PTBA3150009SS
12
4
33.75 (85.7)
22.13 (56.2)
7.63 (19.4)
255 (116.0)
15.0
PTBA3150015SS
12
4
35.13 (89.2)
22.13 (56.2)
12.38 (31.4)
385 (175.0)
22.5
PTBA3150022SS
18
6
38.25 (97.2)
30.25 (76.8)
13.38 (34.0)
535 (243.0)
30.0
PTBA3150030SS
24
8
43.75 (111.1)
33.00 (83.8)
13.75 (34.9)
680 (308.0)
480 VOLTS
208Y/120 VOLTS
MAXIMUM RATING
PRIMARY
SECONDARY
OF
KVA
BREAKER
MAIN
SECONDARY BREAKERS
9.0
ED43B025L (25A)
Q330 (30A)
25 amps
15.0
ED43B040L (40A)
Q350 (50A)
40 amps
22.5
ED43B070L (70A)
Q370 (70A)
60 amps
30.0
ED43B090L (90A)
Q3100 (100A)
80 amps
1...,97,98,99,100,101,102,103,104,105,106 108,109,110,111,112,113,114,115,116,117,...150