ACM_CAT_007_0913 - page 123

ACME ELECTRIC
MILWAUKEE, WI
800.334.5214
acmetransformer.com
123
GENERAL
ELECTRICAL CONNECTION DIAGRAMS
ACME
®
TR NSF RMER
WIRIN DI GRAMS
PRIMARY: 240 X 480
SECONDARY: 120/240
TAPS: None
X4
X1
H4
H2
H3
H1
X2
X3
PRIMARY: 240 X 480
SECONDARY: 120/240
2, 2
1
/
2
% ANFC, 4, 2
1
/
2
% BNFC
X4
X1
H10
H2 H3
H1
X2
X3
H5 H6
H8 H7
H4
H9
Connect
Connect
Primary Primary
Inter-
Secondary
Volts
Lines To Connect
Lines To
216
H1-H10 H1 to H9
H10 to H2
228
H1-H10 H1 to H8
H10 to H3
240
H1-H10 H1 to H7
H10 to H4
252
H1-H10 H1 to H6
H10 to H5
432
H1-H10 H2 to H9
444
H1-H10 H3 to H9
456
H1-H10 H3 to H8
468
H1-H10 H4 to H8
480
H1-H10 H4 to H7
492
H1-H10 H5 to H7
504
H1-H10 H5 to H6
Secondary Volts
240
X2 to X3
X1-X4
120/240
X2 to X3 X1-X3-X4
120
X1 to X3
X1-X4
X2 to X4
PRIMARY: 240 X 480
SECONDARY: 120/240
TAPS: 2, 2
1
/
2
% ANFC, 2, 2
1
/
2
% BNFC
X4
X1
2
H1
X2
X3
H3
1 3
H4
4 5 6 7 8
H2
Connect
Connect
Primary Primary
Inter-
Secondary
Volts
Lines To Connect
Lines To
480
H1-H4 H2 to H3
240
H1-H3 &
H2-H4
Secondary Volts
240
X2 to X3
X1-X4
120/240
X2 to X3 X1-X2-X4
120
X1 to X3
X1-X4
X2 to X4
PRIMARY: 208
SECONDARY: 120/240
TAPS: 2, 5% BNFC
X4
X1
H1
X2
X3
H3
H4
H2
Connect
Connect
Primary Primary
Inter-
Secondary
Volts
Lines To Connect
Lines To
208
H1 & H4
198
H1 & H3
187
H1 & H2
Secondary Volts
240
X2 to X3
X1-X4
120/240
X2 to X3 X1-X2-X4
120
X1 to X3
X1-X4
X2 to X4
Connect
Connect
Primary Primary
Inter-
Secondary
Volts
Lines To Connect
Lines To
216
H1-H4 H1, H3, 8 &
H2, H4, 1
228
H1-H4 H1, H3, 7 &
H2, H4, 2
240
H1-H4 H1, H3, 6 &
H2, H4, 3
252
H1-H4 H1, H3, 5 &
H2, H4, 4
432
H1-H4 H2, 1 & H3, 8
444
H1-H4 H2, 2 & H3, 8
456
H1-H4 H2, 2 & H3, 7
468
H1-H4 H2, 3 & H3, 7
480
H1-H4 H2, 3 & H3, 6
492
H1-H4 H2, 4 & H3, 6
504
H1-H4 H2, 4 & H3, 5
Secondary Volts
240
X2 to X3
X1-X4
120/240
X2 to X3 X1-X2-X4
120
X1 to X3
X1-X4
X2 to X4
PRIMARY: 240 X 480
SECONDARY: 120/240
TAPS: 2, 2
1
/
2
% ANFC, 2, 2
1
/
2
% BNFC
X4
X1
H8
H2 H3
H1
X2
X3
H4 H5
H6 H7
Connect
Connect
Primary Primary
Inter-
Secondary
Volts
Lines To Connect
Lines To
252
H1-H8 H1 to H5
H4 to H8
240
H1-H7 H1 to H5
H3 to H7
228
H1-H6 H1 to H5
H2 to H6
504
H1-H8 H4 to H5
492
H1-H8 H3 to H5
480
H1-H7 H3 to H5
468
H1-H7 H2 to H5
456
H1-H6 H2 to H5
Secondary Volts
240
X2 to X3
X1-X4
120/240
X2 to X3 X1-X2-X4
120
X1 to X3
X1-X4
X2 to X4
PRIMARY: 240 X 480
SECONDARY: 120/240
TAPS: None
X4
X1
H4
H2
H3
H1
X2
X3
Connect
Connect
Primary Primary
Inter-
Secondary
Volts
Lines To Connect
Lines To
480
H1-H4 H2 to H3
240
H1-H3 &
H2-H4
Secondary Volts
240
X2 to X3
X1-X4
120/240
X2 to X3 X1-X2-X4
120
X1 to X3
X1-X4
X2 to X4
1
2
3
6
5
4
Wiring Diagrams
Sections I, II, III & IV
1...,113,114,115,116,117,118,119,120,121,122 124,125,126,127,128,129,130,131,132,133,...150
Powered by FlippingBook