SECTION
DRY-TYPE DISTRIBUTION TRANSFORMERS
ACME ELECTRIC
•
MILWAUKEE, WI
•
800.334.5214
•
acmetransformer.com
29
①
Wall mounting brackets use PL-79911.
②
If used on unbalanced loads, these units should only be used on a 4 wire
system with the supply neutral connected to the transformer. If used on
balanced loads, such as motor loads, then they may be used on a 3 wire
system without a neutral or 4th wire.
③
These units are encapsulated with a 115° C temperature rise.
④
These units are ventilated with 150° C temperature rise.
⑤
Wall mounting brackets use PL-79912.
190/200/208/220/240 DELTA PRIMARY VOLTS –– 400Y/231 SECONDARY VOLTS –– 3Ø, 60 Hz
GROUP V
APPROX. DIMENSIONS
APPROX.
TYPE MTG.
Weather Wiring Diagrams &
kVA CATALOG NO.
Inches (Cm.)
SHIP WEIGHT W – Wall
Knockouts Shield
Design Figures
Height
Width
Depth
Lbs. (Kg.)
F – Floor
Inches (Cm.)
P/N
Begin on Page 122
15.0 T379083S
18.86 (47.9)
20.30 (51.6)
9.03 (22.9)
300 (136.1)
F
①
NA
NA
75-I
30.0 TP79085S
29.90 (75.9)
28.15 (71.5)
22.37 (56.8)
511 (231.8)
F
⑤
NA
WSA2
74-E
45.0 TP79087S
25.50 (64.8)
24.39 (62.0)
19.37 (49.2)
540 (244.9)
F
⑤
NA
WSA1
74-E
75.0 TP79088S
35.90 (91.2)
31.90 (81.0)
26.88 (68.3)
703 (318.9)
F
NA
WSA3
74-E
AUTO-TRANSFORMERS
600 PRIMARY VOLTS –– 480 SECONDARY VOLTS –– 3Ø, 60 Hz
480 PRIMARY VOLTS –– 380 SECONDARY VOLTS –– 3Ø, 50/60 Hz ALTERNATE RATING
kVA
APPROX. DIMENSIONS
APPROX.
TYPE MTG.
Weather Wiring Diagrams &
600 Pri.
480 Pri.
CATALOG NO.
Inches (Cm.)
SHIP WEIGHT W – Wall
Knockouts Shield
Design Figures
480V Sec. 380 Sec.
Height
Width
Depth
Lbs. (Kg.)
F – Floor
Inches (Cm.)
P/N
Begin on Page 122
15.0
12.0 T2527031
③
15.21 (38.6) 19.25 (48.9)
7.37 (18.7)
104 (47.2)
W
NA
NA
56–F
30.0
24.0 T2527051
③
15.21 (38.6) 19.25 (48.9)
7.37 (18.7)
152 (68.9)
W
NA
NA
56–F
45.0
36.0 T2527071
③
15.21 (38.6) 19.25 (48.9)
7.37 (18.7)
156 (70.8)
W
NA
NA
56–F
75.0
60.0 T3527101
③
18.86 (47.9) 20.30 (51.6)
9.03 (22.9)
300 (136.1)
F
①
NA
NA
56–I
112.5 90.0 T2A527121
④
25.50 (64.8) 24.40 (62.0) 19.40 (49.3)
325 (147.0)
F
⑤
NA
WSA1
57–E
150.0 120.0 T2A527131
④
25.50 (64.8) 24.40 (62.0) 19.40 (49.3)
350 (158.8)
F
⑤
NA
WSA1
57–E
225.0 180.0 T2A527151
④
29.41 (74.7) 28.15 (71.5) 22.37 (56.8)
600 (272.0)
F
⑤
NA
WSA2
57–E
300.0 240.0 T2A527171
④
29.41 (74.7) 28.15 (71.5) 22.37 (56.8)
650 (294.8)
F
⑤
NA
WSA2
57–E
450.0 360.0 T2A527181
④
35.47 (90.1) 31.90 (81.0) 26.88 (68.3)
750 (340.0)
F
NA
WSA3
57–E
500.0 400.0 T2A527191
④
35.47 (90.1) 31.90 (81.0) 26.88 (68.3)
790 (358.3)
F
NA
WSA3
57–E
Notes: 15.0 kVA unit encapsulated (TP1 exempt), 30.0 through 75.0 kVA units TP1 compliant
Notes: Auto-Transformers TP1 exempt