Table of Contents Table of Contents
Previous Page  132 / 244 Next Page
Information
Show Menu
Previous Page 132 / 244 Next Page
Page Background

B u c k - B o o s t T r a n s f o r m e r s

Selection Charts

132

Three Phase Application

Boosting

Bucking

Line Voltage

(Available)

399Y

230

380

430 440 460

460

480 480

440 440 460 460 480 480 500

500

Load Voltage

(Output)

480Y

277

420

473 462 506

483

528 504

400 419 438 418 457 436 455

477

Catalog Number

T181061

Load

kVA

0.86 0.76 0.85 1.66 0.91 1.74 0.95 1.82

0.79 1.58 1.66 0.83 1.73 0.86 0.90 1.80

Amps

1.04 1.04 1.04 2.08 1.04 2.08 1.04 2.08

1.14 2.18 2.18 1.14 2.18 1.14 1.14 2.18

Maximum Size of

Fuse or Breaker

3

3

3

6

3

6

3

6

3

6

6

3

6

3

3

6

T181062

Load

kVA

1.73 1.51 1.70 3.33 1.82 3.48 1.90 3.63

1.59 3.17 3.31 1.66 3.46 1.73 1.80 3.61

Amps

2.08 2.08 2.08 4.16 2.08 4.16 2.08 4.16

2.29 4.37 4.37 2.29 4.37 2.29 2.29 4.37

Maximum Size of

Fuse or Breaker

6

6

6

10

6

10

6

10

6

10

10

6

10

6

6

10

T181063

Load

kVA

2.60 2.27 2.56 4.99 2.73 5.22 2.85 5.45

2.38 4.75 4.97 2.48 5.19 2.59 2.70 5.41

Amps

3.12 3.12 3.12 6.24 3.12 6.25 3.12 6.24

3.43 6.55 6.55 3.43 6.55 3.43 3.43 6.55

Maximum Size of

Fuse or Breaker

10

6

6

15

6

15

6

15

6

15

15

6

15

6

6

15

T181064

Load

kVA

4.33 3.78 4.26 8.32 4.56 8.70 4.76 9.08

3.96 7.92 8.28 4.14 8.64 4.32 4.51 9.02

Amps

5.20 5.20 5.20 10.40 5.20 10.40 5.20 10.40

5.72 10.92 10.92 5.72 10.92 5.72 5.72 10.92

Maximum Size of

Fuse or Breaker

15

10

10

15

10

15

10

15

10

15

15

10

15

10

10

15

T181065

Load

kVA

8.60 7.56 8.52 16.64 9.11 17.40 9.51 18.16

7.93 15.85 16.57 8.28 17.29 8.64 9.02 18.04

Amps

10.40 10.40 10.40 20.80 10.40 20.80 10.40 20.80

11.44 21.84 21.84 11.44 21.84 11.44 11.44 21.84

Maximum Size of

Fuse or Breaker

20

15

15

30

15

30

15

30

15

30

30

15

30

15

15

30

T181066

Load

kVA

12.90 11.34 12.77 24.97 13.67 26.10 14.27 27.24

11.89 23.77 24.85 12.42 25.93 12.96 13.52 27.07

Amps

15.60 15.60 15.60 31.20 15.60 31.20 15.60 31.20

17.16 32.76 32.76 17.16 32.76 17.16 17.16 32.76

Maximum Size of

Fuse or Breaker

25

25

25

45

25

45

25

45

20

40

40

20

40

20

20

40

T137920

Load

kVA

17.30 15.12 17.03 33.29 18.23 34.80 19.02 36.31

15.85 31.70 33.14 16.57 34.57 17.28 18.03 36.09

Amps

20.80 20.80 20.80 41.60 20.80 41.60 20.80 41.60

22.88 43.68 43.68 22.88 43.68 22.88 22.88 43.68

Maximum Size of

Fuse or Breaker

35

30

30

60

30

60

30

60

30

60

60

30

60

30

30

60

T137921

Load

kVA

25.90 22.69 25.55 49.93 27.34 52.20 28.53 54.47

23.78 47.55 49.71 24.85 51.86 25.92 27.05 54.13

Amps

31.20 31.20 31.20 62.40 31.20 62.40 31.20 62.40

34.32 65.52 65.52 34.32 65.52 34.32 34.32 65.52

Maximum Size of

Fuse or Breaker

50

45

45

90

45

90

45

90

40

80

80

40

80

40

40

80

T137922

Load

kVA

34.60 30.25 34.07 66.58 36.46 69.60 38.04 72.63

31.70 63.40 66.27 33.13 69.15 34.56 36.06 72.18

Amps

41.60 41.60 41.60 83.20 41.60 83.20 41.60 83.20

45.76 87.36 87.36 45.76 87.36 45.76 45.76 87.36

Maximum Size of

Fuse or Breaker

70

60

60

110

60

110

60

110

60

110 110

60

110

60

60

110

T137923

Load

kVA

52.00 45.45 51.18 100.03 54.69 104.57 57.07 109.12 47.63 95.25 99.57 49.77 103.89 51.92 54.18 108.44

Amps

62.50 62.50 62.50 125.00 62.50 125.00 62.50 125.00 68.75 131.25 131.25 68.75 131.25 68.75 68.75 131.25

Maximum Size of

Fuse or Breaker

100

90

90

175

90

175

90

175

80

175 175

80

175

80

80

175

T137924

Load

kVA

86.10 75.62 85.17 166.44 91.15 174.01 95.11 181.57 79.26 158.50 165.69 82.83 172.87 86.39 90.16 180.44

Amps

104.00 104.00 104.00 208.00 104.00 208.00 104.00 208.00 114.40 218.40 218.40 114.40 218.40 114.40 114.40 218.40

Maximum Size of

Fuse or Breaker

175

150

150

300

150

300

150

300

150 300 300 150 300 150

150

300

T243570

Load

kVA

129.30 113.43 127.75 249.66 136.72 261.01 142.67 272.36 118.89 237.75 248.53 124.24 259.31 129.59 135.23 270.66

Amps

156.00 156.00 156.00 312.00 156.00 312.00 156.00 312.00 171.60 327.60 327.60 171.60 327.60 171.60 171.60 327.60

Maximum Size of

Fuse or Breaker

250

225

225

450

225

450

225

450

200 400 400 200 400 200

200

400

T243571

Load

kVA

173.10 151.25 170.33 332.89 182.29 348.02 190.22 363.15 158.52 317.00 331.37 165.65 345.75 172.78 180.31 360.88

Amps

208.00 208.00 208.00 416.00 208.00 416.00 208.00 416.00 228.80 436.80 436.80 228.80 436.80 228.80 228.80 436.80

Maximum Size of

Fuse or Breaker

350

300

300

600

300

600

300

600

300 600 600 300 600 300

300

600

Quantity Required

3

2

2

2

2

2

2

2

2

2

2

2

2

2

2

2

See Page 136-137

for Connection Diagrams

F-F B-B B-B G-G B-B G-G B-B G-G E-E C-C C-C E-E C-C E-E E-E C-C

See chart on page 135.

NOTE: (1) Inputs and Outputs may be reversed; kVA capacity remains constant. All applications above bold face line are suitable for 50/60 Hz. All applications below bold face line are sui able for

60 Hz only. (2) Connection Diagrams A-A and F-F cannot be reverse connected.