B u c k - B o o s t T r a n s f o r m e r s

Selection Charts

128

Single Phase Application

Boosting

Bucking

Line Voltage

(Available)

95

100 105 208 215 215 220 225

135 240 240 245 250 255

Load Voltage

(Output)

120 114 119 240 244 230 235 240

119 208 225 230 234 239

Catalog Number

T181054

Load

kVA

0.19 0.36 0.37 0.38 0.38 0.72 0.73 0.75

0.42 0.37 0.75 0.77 0.78 0.80

Amps

1.56 3.13 3.13 1.56 1.56 3.13 3.13 3.13

3.54 1.77 3.33 3.33 3.33 3.33

Maximum Size of

Fuse or Breaker

6

6

6

6

6

6

6

6

6

3

6

6

6

6

T181055

Load

kVA

0.38 0.71 0.74 0.75 0.76 1.44 1.47 1.50

0.84 0.74 1.50 1.53 1.56 1.59

Amps

3.13 6.25 6.25 3.13 3.13 6.25 6.25 6.25

7.08 3.54 6.67 6.67 6.67 6.67

Maximum Size of

Fuse or Breaker

10

15

6

6

15

15

15

15

15

6

15

15

15

15

T181056

Load

kVA

0.56 1.07 1.12 1.13 1.14 2.16 2.20 2.25

1.26 1.11 2.25 2.30 2.34 2.39

Amps

4.69 9.38 9.38 4.69 4.69 9.38 9.38 9.38

10.63 5.31 10.00 10.00 10.00 10.00

Maximum Size of

Fuse or Breaker

10

15

15

10

10

15

15

15

15

6

15

15

15

15

T181057

Load

kVA

0.94 1.78 1.86 1.88 1.91 3.59 3.67 3.75

2.11 1.84 3.75 3.83 3.90 3.98

Amps

7.81 15.63 15.63 7.81 7.81 15.63 15.63 15.63 17.71 8.85 16.67 16.67 16.67 16.67

Maximum Size of

Fuse or Breaker

15

25

25

15

15

25

25

25

20

15

20

20

20

20

T181058

Load

kVA

1.88 3.56 3.72 3.75 3.81 7.19 7.34 7.50

4.21 3.68 7.50 7.67 7.80 7.97

Amps

15.63 31.25 31.25 15.63 15.63 31.25 31.25 31.25 35.42 17.71 33.33 33.33 33.33 33.33

Maximum Size of

Fuse or Breaker

25

45

45

25

25

45

45

45

40

20

40

40

40

40

T181059

Load

kVA

2.81 5.34 5.58 5.63 5.72 10.78 11.02 11.25

6.32 5.53 11.25 11.50 11.70 11.95

Amps

23.44 46.88 46.88 23.44 23.44 46.88 46.88 46.88 53.13 26.56 50.00 50.00 50.00 50.00

Maximum Size of

Fuse or Breaker

40

70

70

40

40

70

70

70

60

30

60

60

60

60

T113073

Load

kVA

3.75 7.13 7.44 7.50 7.63 14.38 14.69 15.00

8.43 7.37 15.00 15.33 15.60 15.93

Amps

31.25 62.50 62.50 31.25 31.25 62.50 62.50 62.50 70.83 35.42 66.67 66.67 66.67 66.67

Maximum Size of

Fuse or Breaker

50

90

90

50

50

90

90

90

80

40

80

80

80

80

T113074

Load

kVA

5.63 10.69 11.16 11.25 11.44 21.56 22.03 22.50 12.64 11.05 22.50 23.00 23.40 23.90

Amps

46.90 93.80 93.80 46.90 46.90 93.80 93.80 93.80 106.30 53.10 100.00 100.00 100.00 100.00

Maximum Size of

Fuse or Breaker

80

150 150

70

70

125 125 125

125 60 125 125 125 125

T113075

Load

kVA

7.50 14.25 14.88 15.00 15.25 28.75 29.38 30.00 16.86 14.73 30.00 30.67 31.20 31.87

Amps

62.50 125.00 125.00 62.50 62.50 125.00 125.00 125.00 141.70 70.80 133.30 133.30 133.30 133.30

Maximum Size of

Fuse or Breaker

100 200 200

90

90

175 175 175

175 80 175 175 175 175

T113076

Load

kVA

11.25 21.38 22.31 22.50 22.88 43.13 44.06 45.00 25.29 22.10 45.00 46.00 46.80 47.80

Amps

93.80 187.50 187.50 93.80 93.80 187.50 187.50 187.50 212.50 106.30 200.00 200.00 200.00 200.00

Maximum Size of

Fuse or Breaker

150 300 300 150 150 250 250 250

250 125 250 250 250 250

T113077

Load

kVA

18.75 35.63 37.19 37.50 38.13 71.88 73.44 75.00 42.15 36.83 75.00 76.67 78.00 79.67

Amps

156.30 312.50 312.50 156.30 156.30 312.50 312.50 312.50 354.20 177.10 333.30 333.30 333.30 333.30

Maximum Size of

Fuse or Breaker

250 450 450 225 225 450 450 450

400 200 400 400 400 400

T213078

Load

kVA

28.10 53.40 55.80 56.30 57.20 107.80 110.20 112.50 63.20 55.30 112.50 115.00 117.00 119.50

Amps

234.40 468.80 468.80 234.40 234.40 468.80 468.80 468.80 531.30 265.60 500.00 500.00 500.00 500.00

Maximum Size of

Fuse or Breaker

400 700 700 350 350 700 700 700

600 300 600 600 600 600

T213079

Load

kVA

37.50 71.30 74.40 75.00 76.30 143.80 146.90 150.00 84.30 73.70 150.00 153.30 156.00 159.30

Amps

312.50 625.00 625.00 312.50 312.50 625.00 625.00 625.00 708.30 354.20 666.70 666.70 666.70 666.70

Maximum Size of

Fuse or Breaker

500 1000 1000 450 450 1000 1000 1000

800 400 800 800 800 800

See Page 136 for Connection Diagrams D C C H H G G G

F

I

E

E

E

E

See chart on page 135.

NOTE: Inputs and Outputs may be reversed; kVA capacity remains constant. All applications above bold face line are suitable for 50/60 Hz. All applications below bold face line are suitable for 60 Hz only.

With larger kVA buck-boost units, it is necessary to utilize multiple conductors on the secondary (X) terminals as shown in the chart on page 135.