ACME ELECTRIC
•
MILWAUKEE, WI
•
800.334.5214
•
acmetransformer.com
55
SECTION
TA SERIES OPEN CORE & COIL INDUSTRIAL CONTROL TRANSFORMERS
Q
Mount secondary fuse clips on terminals
X1 and F or F1 using the screws supplied
with the transformer.
Q
Connect secondary load lines to terminals
X2 and F or F2.
Q
Use dual-element slow-blowing fuses
such as Bussmann MFG., Fusetron Type
FNM, Littelfuse or Shawmut (not supplied
with fuse kits).
PL112600/601 Fuse Kit
PL112602 Fuse Kit
1.
To attach secondary fuse kit PL-112603 to primary fuse
kits PL112700 thru PL112707 snap the secondary single
pole fuse block onto the unlabeled side of the primary
double pole fuse block. (See Figure 1)
2.
Install the fuse kits as instructed under the primary fuse kit
instructions on page 54.
3.
Select the appropriate pair of jumpers for making the
connections between the secondary fuse block and the
secondary (X-side) of the transformer.
4.
Connect the female quick-connect of the jumpers
supplied to one of the male quick-connects of the
secondary fuse block - one jumper to each end of
the fuse block. (See Figure 2)
5.
Connect the ring terminal of the jumpers supplied
to screw terminals X1 and F or F1 on the secondary
(X-side) of the transformer.
6.
Connect secondary load lines to terminals
X2 and F or F2.
SECONDARY (X SIDE)
Figure 1
Figure 2
Jumper Link Connections
Group A Series: 240 V parallel: 120 V
Group B Series: 480 V parallel: 240 V
Group F series: 230 V parallel: 115 V
Group I Series: 24 V parallel: 12 V
Group J Series: 480 V & 240 V: 240 V & 120 V
Group K Series: 240 V: 120 V
TA Series Instructions for Secondary Fuse Kit
Type PL112603: use dual element slow-blow fuse 13/32" x 1-1/2" (1.0 x 3.8 cm)
Series
Connection
Parallel
Connection
Exception:
150 VA transformer TA232404 does not have
quick connect terminals.
TA Series Secondary Fuse Kits
Type PL112600, 601, 602: Use Dual Element Slow-Blow Fuse