G e n e r a l
Diagrams
210
EXPORT MODEL
PRIMARY: 190-220 x 380-440
SECONDARY: 120/240
X4
X1
H5
H3
H1
X2
X3
H2 H4
H6
H7 H8 H9
H10
Connect
Connect
Primary Primary
Inter-
Secondary
Volts
Lines To
Connect
Lines To
190
H1 & H7
H1 to H6
H2 to H7
200
H1 & H8
H1 to H6
H3 to H8
208
H1 & H9
H1 to H6
H4 to H9
220
H1 & H10
H1 to H6
H5 to H10
380
H1 & H7
H2 & H6
400
H1 & H8
H3 & H6
416
H1 & H9
H4 & H6
440
H1 & H10
H5 & H6
Secondary Volts
240
X2 to X3
X1-X4
120/240
X2 to X3
X1-X2-X4
120
X1 to X3
X1-X4
X2 to X4
14
PRIMARY: 600
SECONDARY: 120/240
TAPS: None
X4
X1
H1
X2
X3
H2
Connect
Connect
Primary Primary
Inter-
Secondary
Volts
Lines To
Connect
Lines To
600
H1-H2
Secondary Volts
240
X2 to X3
X1-X4
120/240
X2 to X3
X1-X2-X4
120
X1 to X3
X1-X4
X2 to X4
9
PRIMARY: 600
SECONDARY: 120/240
TAPS: 2, 5% BNFC
X4
X1
H1
X2
X3
H3
H4
H2
Connect
Connect
Primary Primary
Inter-
Secondary
Volts
Lines To
Connect
Lines To
600
H1-H4
570
H1-H3
540
H1-H2
Secondary Volts
240
X2 to X3
X1-X4
120/240
X2 to X3
X1-X2-X4
120
X1 to X3
X1-X4
X2 to X4
10
PRIMARY: 600
SECONDARY: 120/240
TAPS: 2, 2
1
/
2
% ANFC, 4, 2
1
/
2
% BNFC
X4
X1
1
H1
X2
X3
2
H2
3 4 5 6
Connect
Connect
Primary Primary
Inter-
Secondary
Volts
Lines To
Connect
Lines To
540
H1-H2
1-6
555
H1-H2
1-5
570
H1-H2
2-6
585
H1-H2
2-5
600
H1-H2
3-5
615
H1-H2
2-4
635
H1-H2
3-4
Secondary Volts
240
X2 to X3
X1-X4
120/240
X2 to X3
X1-X2-X4
120
X1 to X3
X1-X4
X2 to X4
11
PRIMARY: 240
SECONDARY: 120/240
TAPS: None
1
1
2
3
3
Connect
Connect
Primary Primary
Inter-
Secondary
Volts
Lines To
Connect
Lines To
240
1-3
Secondary Volts
240
1-3
120
1-2 or 2-3
120/240
1-2-3
12
Input ConnectionsInsulate
&
Volts
Connect
Insulate
120
1, 3, 6, 8 to A
4, 9
2, 5, 7, 10 to B
1, 6 to A
208
4, 9 to B
5, 10
2, 3 to C
7, 8 to D
1, 6 to A
240
5, 10 to B
4, 9
2, 3 to C
7, 8 to D
1 to A
10 to B
480
2, 3 to C
4, 9
5, 6 to D
7, 8 to E
Output Connections
Output
Lines
Volts
Connect
To
11 to F
120
12 to G
F, G
14 to H
11 to F
120/240
12 to G
F, G, H
14 to H
11 to F
208
12 to G
F, H
13 to H
11 to F
240
12 to G
F, H
14 to H
NOTE:
To prevent externally shorting, all leads marked
“INSULATE” must be individually capped with wire
nuts or equivalent. Insulate leads individually!
POWER LINE CONDITIONER
2
F
1
3
H
4
5
6
7
8
G
9
10
11
12
13
14
B
C
D
E
A
INPUT LINE
16
PRIMARY: 208 Volts
SECONDARY: 120/240 Volts
TAPS:
17
H1
1 2 3
H2
4 5 6
X1
X3
X2
X4
Connect
Connect
Primary Primary
Inter-
Secondary
Volts
Lines To
Connect
Lines To
218
H1 & H2
3 to 4
213
H1 & H2
2 to 4
208
H1 & H2
3 to 5
203
H1 & H2
2 to 5
198
H1 & H2
1 to 5
192
H1 & H2
2 to 6
187
H1 & H2
1 to 6
Secondary Volts
240
X2 to X3
X1-X4
120/240
X2 to X3
X1-X2-X4
120
X1 to X3
X2 to X4
X1-X4