Table of Contents Table of Contents
Previous Page  73 / 244 Next Page
Information
Show Menu
Previous Page 73 / 244 Next Page
Page Background

6

73

toll free 800.334.5214 ACME ELECTRIC |

hubbell-acmeelectric.com

I n d u s t r i a l C o n t r o l T r a n s f o r m e r s

Table 2 Typical Magnetic Motor Starter and Contractor Data

60 Hz, 120 Volt, 3-Pole

N.E.M.A. Size

Contractor

00

0

1

2

3

4

5

A

L

Allen

Bradley

500 Series

192

192

240

660

1225

2040

1490

VA Inrush

29

29

29

45

69

110

96

VA Sealed

K Series

53

110

175

240

580

1000

1950

VA Inrush

15

20

22

31

43

65

98

VA Sealed

ASEA

Heavy

5

85

100

150

490

900

1200

VA Inrush

Duty

9

9

11.5

15

35

55

65

VA Sealed

Furnas

218

218

218

218

310

957

1518

VA Inrush

25

25

25

25

26

75

116

VA Sealed

General

Electric

151

151

151

528

1152

1248

2580

VA Inrush

24

24

24

60

83

86

191

VA Sealed

Joslyn Clark

210

210

210

210

724

880

1790

VA Inrush

18

18

18

18

30

39

295

VA Sealed

Siemens-

Allis

76

76

76

194

365

530

1630

VA Inrush

12

12

12

21

35

40

110

VA Sealed

Square D

165

245

245

311

700

1185

2970

VA Inrush

33

27

27

37

46

85

212

VA Sealed

Westinghouse

160

160

160

160

625

625

1700

VA Inrush

25

25

25

25

50

50

180

VA Sealed

Cutler

Hammer

(Citation

Line)

A1 Series

87

103

103

1158

VA Inrush

15

20

20

100

VA Sealed

B1 Series

102

103

103

140

390

1158

1158

VA Inrush

13

20

20

24

50

100

100

VA Sealed

Data is most current at time of printing. Contact individual manufacturer for updates.