6
73
toll free 800.334.5214 ACME ELECTRIC |
hubbell-acmeelectric.comI n d u s t r i a l C o n t r o l T r a n s f o r m e r s
Table 2 Typical Magnetic Motor Starter and Contractor Data
①
60 Hz, 120 Volt, 3-Pole
N.E.M.A. Size
Contractor
00
0
1
2
3
4
5
A
L
Allen
Bradley
500 Series
—
192
192
240
660
1225
2040
1490
VA Inrush
—
29
29
29
45
69
110
96
VA Sealed
K Series
53
110
175
240
580
1000
1950
VA Inrush
15
20
22
31
43
65
98
VA Sealed
ASEA
Heavy
5
85
100
150
490
900
1200
VA Inrush
Duty
9
9
11.5
15
35
55
65
VA Sealed
Furnas
218
218
218
218
310
957
1518
VA Inrush
25
25
25
25
26
75
116
VA Sealed
General
Electric
151
151
151
528
1152
1248
2580
VA Inrush
24
24
24
60
83
86
191
VA Sealed
Joslyn Clark
210
210
210
210
724
880
1790
VA Inrush
18
18
18
18
30
39
295
VA Sealed
Siemens-
Allis
76
76
76
194
365
530
1630
VA Inrush
12
12
12
21
35
40
110
VA Sealed
Square D
165
245
245
311
700
1185
2970
VA Inrush
33
27
27
37
46
85
212
VA Sealed
Westinghouse
160
160
160
160
625
625
1700
VA Inrush
25
25
25
25
50
50
180
VA Sealed
Cutler
Hammer
(Citation
Line)
A1 Series
87
103
103
—
—
—
1158
VA Inrush
15
20
20
—
—
—
100
VA Sealed
B1 Series
102
103
103
140
390
1158
1158
VA Inrush
13
20
20
24
50
100
100
VA Sealed
①
Data is most current at time of printing. Contact individual manufacturer for updates.