Table of Contents Table of Contents
Previous Page  90 / 244 Next Page
Information
Show Menu
Previous Page 90 / 244 Next Page
Page Background

90

toll free 800.334.5214 ACME ELECTRIC |

hubbell-acmeelectric.com

I n d u s t r i a l C o n t r o l T r a n s f o r m e r s

6

INDUSTRIAL CONTROLTRANSFORMERS FOR HARSH ENVIRONMENTS

Designed for control panels where internal installation of Control Transformers is prohibited

Some specifications require installation of large control transformers, usually 1000 to 5000 VA outside the control cabinet. This means the

transformer must be in a sheet metal enclosure instead of the usual open core and coil construction method.

Acme meets this need by providing all of the power, protection, regulation and performance of our standard industrial control transformers

in one UL -3R enclosure. These transformers are wound with copper magnet wire, deliver full nameplate capacity, and provide the high

regulation required in control applications.

Voltage combinations available are: 240 x 480V primary, 120V secondary and 240/480/600V primary, 120/100V secondary.

Ratings available are 1000, 2000, 3000 and 5000 VA. All units are UL listed, CSA certified, and covered by Acme’s exclusive

10-year limited warranty.

Features

Q

Fully encapsulated and enclosed

Q

55°C temperature rise, 155°C insulation

Q

Copper windings

Q

1000, 2000, 3000, 5000 and 10000 VA sizes

Q

Voltage regulation exceeds NEMA requirements

Q

UL and UL-3R listed

Q

CSA certified

Q

10-year limited warranty

240/480/600 PRIMARY VOLTS — 120/100 SECONDARY VOLTS — 1Ø, 50/60 Hz

VA

Rating

Catalog

Number

Output

Amps

Height

(Inches)(Cm.)

Width

(Inches)(Cm.)

Depth

(Inches)(Cm.)

Weight

(Lbs.)(Kg.)

Wiring Diagram

① ②

2000

T153929

16.67

14.77

10.31

7.13

80

C

(37.5)

(26.2)

(18.1)

(36.3)

3000

T153930

25.00

13.85

13.25

10.19

130

C

(35.2)

(33.7)

(25.9)

(59.0)

5000

T153931

41.67

13.85

13.25

10.19

140

C

(35.2)

(33.7)

(25.9)

(63.5)

See page 88 for electrical diagram.

See page 78 for fuse sizing information.

}

For secondary fuse size, multiply output amps x 1.25.

240 X 480 PRIMARY VOLTS — 120 SECONDARY VOLTS — 1Ø, 50/60 Hz

VA

Rating

Catalog

Number

Output

Amps

Height

(Inches)(Cm.)

Width

(Inches)(Cm.)

Depth

(Inches)(Cm.)

Weight

(Lbs.)(Kg.)

Wiring Diagram

① ②

1000

T181217

8.33

13.10

10.31

7.13

55

B

(33.3)

(26.2)

(18.1)

(24.9)

2000

T181219

16.67

14.77

10.31

7.13

80

B

(37.5)

(26.2)

(18.1)

(36.3)

3000

T181220

25.00

14.77

10.31

7.13

100

B

(37.5)

(26.2)

(18.1)

(45.4)

5000

T181221

41.67

13.85

13.25

10.19

140

B

(35.2)

(33.7)

(25.9)

(63.5)

10000

T181223

83.3

16.47

13.88

12.94

308

B

(41.8)

(35.3)

(32.9)

(139.7)

See page 88 for electrical diagram.

See page 78 for fuse sizing information.

For secondary fuse size, multiply output amps x 1.25.

Encapsulated

1000 VA–10000 VA

D

H

W